Firewall (Cable)
Tested for Propagation of fire up to two hours by National Test House.
- ASTME 119/ BS 476 (As per Pt. 20 and 24)
- IS: 162:1950
Even the smallest of fires from a short circuit or external source can easily cause an enormous loss to property and life. Electrical cables are a natural pathway for a fire to spread rapidly. With Fire Security cable coatings applied the possibility of a fire spreading through the cable routing is eliminated. Firewall offers spread of fire up to two hours which is more than sufficient time to get help.
Additional Product Information:
Application viscosity: Thixotropic / Ready to Use
Mix Ratio: Not applicable
Typical Film Thickness: 130 to 170 microns dry (single coat)
Required film thickness depends on fire ratings
Theoretical Coverage: 9(m2/lt) at 130 microns DFT.
Method of Application: Airless Spray, Brush, Roller.
Drying Information: Ambient Temperature (25°C)
Touch Dry: 2 Hours
Hard Dry: 4-5 Hours(Recoating Interval: Min. 5 hours)
Viscosity: 90 - 110
Approx. Weights: 1.3 ± 0.3kg per ltr.
Shelf Life: 12 months from date of packing
Fire Rating | Average Dry Thickness (Firewall) |
---|---|
30 min. | 250 microns |
60 min. | 350 - 450 microns |
120 min. | 550 - 700 microns |
In continuously improving technology there has been a swing towards the use of thin film intumescent coatings to achieve same traditional results